IEC 60079-0 — General Requirements for Ex Equipment
IEC 60079-0 is the foundation of the IEC 60079 series, setting general requirements that apply to all Ex equipment regardless of the specific protection type. Understanding IEC 60079-0 provides the framework within which all other parts of the series operate.
What IEC 60079-0 Covers
- Definitions — explosive atmosphere, hazardous area, EPL, gas group, temperature class
- General construction requirements — materials, fasteners, surfaces
- Electrical requirements — creepage and clearance distances
- Temperature limits — equipment surface temperature and T-class
- Marking requirements — Ex marking plate content and format
- Documentation requirements — for certification and installation
Equipment Protection Levels (EPL)
IEC 60079-0 introduces the concept of Equipment Protection Levels (EPL), which categorises equipment by its likelihood of becoming an ignition source:
| EPL | Description | Zone |
|---|---|---|
| Ga | Very high protection — equipment for Zone 0 | Zone 0 |
| Gb | High protection — equipment for Zone 1 and above | Zone 1 |
| Gc | Enhanced protection — equipment for Zone 2 | Zone 2 |
| Da | Very high protection for dust Zone 20 | Zone 20 |
| Db | High protection for dust Zone 21 | Zone 21 |
| Dc | Enhanced protection for dust Zone 22 | Zone 22 |
EPL Ga equipment can be used in Zone 0, 1, or 2. EPL Gb equipment can be used in Zone 1 or 2 but NOT Zone 0. EPL Gc equipment can only be used in Zone 2. Always verify the EPL on the Ex certificate matches the zone classification of the installation area.
Reading about it is one thing. EX Academy puts you in the scenario — interactive inspection simulations, equipment selection decisions, and 1,185+ practice questions all referenced to IEC 60079. Try Simulation 01 and Scenario 01 completely free.