IEC 60079-0 — General Requirements for Ex Equipment

EX Academy Knowledge Base · IEC 60079 · CompEx Preparation · 2025

IEC 60079-0 is the foundation of the IEC 60079 series, setting general requirements that apply to all Ex equipment regardless of the specific protection type. Understanding IEC 60079-0 provides the framework within which all other parts of the series operate.

What IEC 60079-0 Covers

  • Definitions — explosive atmosphere, hazardous area, EPL, gas group, temperature class
  • General construction requirements — materials, fasteners, surfaces
  • Electrical requirements — creepage and clearance distances
  • Temperature limits — equipment surface temperature and T-class
  • Marking requirements — Ex marking plate content and format
  • Documentation requirements — for certification and installation

Equipment Protection Levels (EPL)

IEC 60079-0 introduces the concept of Equipment Protection Levels (EPL), which categorises equipment by its likelihood of becoming an ignition source:

EPLDescriptionZone
GaVery high protection — equipment for Zone 0Zone 0
GbHigh protection — equipment for Zone 1 and aboveZone 1
GcEnhanced protection — equipment for Zone 2Zone 2
DaVery high protection for dust Zone 20Zone 20
DbHigh protection for dust Zone 21Zone 21
DcEnhanced protection for dust Zone 22Zone 22
EPL and Zone Matching

EPL Ga equipment can be used in Zone 0, 1, or 2. EPL Gb equipment can be used in Zone 1 or 2 but NOT Zone 0. EPL Gc equipment can only be used in Zone 2. Always verify the EPL on the Ex certificate matches the zone classification of the installation area.